Operating Voltage:
24 Vdc (18-32 Vdc)
Current Draw:
210 mA avg., 400 mA peak
Power Consumption
5 W max.
Analog Output:
4-20 mA
Range:
0-100% LEL
Standard Calibrations:
Methane, Propane, and Butane
Other Available Calibrations:**
Hexane, Isobutane, Ethane, Octane, Ethanol, Ethylene, Benzene, Methanol, Ethylene oxide, Ethyl benzene, 1-Butene, Toluene, Cyclohexanone, Propylene, Xylene, Cyctohexanol, n-Butane, Heptane, Dimethylpropane
**Please note that this list is not all inclusive. The IR-6000 can be calibrated for most hydrocarbons, provided a calibration gas is available. For more information, please contact ENMET.
Accuracy:
+/- 3% 0 to 50% LEL
+/- 5% 51 to 100%
|
|
Response Time:
T50 < 5 seconds
T90 < 10 seconds
Temperature Rating:
-40 ° F to +158 ° F
(-40 ° C to + 70 ° C)
Humidity:
0-99% (non-condensing)
Housing Construction:
316 stainless steel
Approvals:
CSA
Classification:
Class 1, Div 1, Groups B,C,D
Ingress Rating:
IP54
Mounting:
3/4" NPT
Size:
6.5" x 2.6" (165 mm x 66 mm)
Weight:
2 lbs (0.9 kg) |